Skip to main content
  1. Home
  2. Products
  3. Check Valves
  4. Check Valves

Fluid Control Equipment

Check Valves

CK Series

Check valves for steam and other fluids

Disc and spring construction assures stable performance with installation in either vertical or horizontal pipelines. TLV CK series check valves are ideal for nearly all types of fluid processes with their high sealing performance in both vertical and horizontal piping and their rapid open-close mechanism.

CK Series Check Valves Pamphlet (198 KB)

 

Benefits and Features

  • Small valve-opening pressure differential.
  • Select between a metal valve seat or a soft valve seat for use with steam, water or air.
  • Available in sizes up to 4 inch on some models.
  • All stainless steel construction (CK3M/CK3T/CK3R also available in brass or bronze).
Reliably Prevents Backflow
  • Check valves utilize a mechanical sealing mechanism to prevent backflow.
  • By providing a tight seal, backflow is safely avoided.
Easy to Use
  • Compact design.
  • There are no restrictions on installation orientation (horizontal, vertical).
  • After the valve has closed, it opens again at the slightest pressure differential.
Long Service Life
  • TLV’s unique center-guided disc (CK3MG, CKF3MG, CKF3RG) offers greater durability.

 

Application Areas

  • Piping that requires backflow prevention.
  • Locations where frequent opening and closing operation is expected.
Screwed Connection
CK3M/CK3T/CK3R: Select among 3 types of sealing surfaces, depending on the temperature and fluid requirements
Applicable FluidsMax. Operating Temperature TMO (°C)Sealing SurfaceModelPhotoSpecifications
Steam220℃MetalCK3MCK3M/CK3T/CK3RSpecifications
Steam, Hot water185℃PTFECK3T
Air, water, hot water90℃Nitrile Rubber (NBR)CK3R
CK3M has a metal seal.CK3T has a PTFE seal.CK3R has a rubber seal.
CK3MG: Center-guided disc and large flow area ensure superior durability and capacity
Applicable FluidsMax. Operating Temperature TMO (°C)Sealing SurfaceModelPhotoSpecifications
Steam, hot water, water220℃MetalCK3MGCK3MGSpecifications
CK3MG has a centre bar with a metal seal.
Wafer-construction (flangeless)
CKF3M/CKF3R: Compact stainless steel check valves
Applicable FluidsMax. Operating Temperature TMO (°C)Sealing SurfaceModelPhotoSpecifications
Steam, hot water, water350℃MetalCKF3MCJF3M/CKF3RSpecifications
Air, water, hot water150℃Fluorine Rubber (FPM)CKF3R
CKF3M has a metal seal.CKF3R has a rubber seal.
CKF3MG/CKF3RG: Center-guided disc and large flow area ensure superior durability and capacity
Applicable FluidsMax. Operating Temperature TMO (°C)Sealing SurfaceModelPhotoSpecifications
Steam, hot water, water350℃MetalCKF3MGCKF3MG/CKF3RGSpecifications
Air, water, hot water150℃Fluorine Rubber (FPM)CKF3RG
CKF3MG has a center bar with a metal seal.CKF3RG has a centre bar with a rubber seal.

 

Product Details

ModelPhotoConnectionBody MaterialApplicable FluidsPMO (MPaG)Min. Opening Differential Pressure (MPa)*TMO (°C)Sealing Surface MaterialSpecificationsManual
CK3MScrewedBrass 
(C3604)
Steam1.00.002220MetalSpecificationsManual
Bronze 
(CAC407)
Stainless Steel 
(ASTM A351 
Gr.CF8)
2.1
CK3TScrewedBrass 
(C3604)
Steam 
Hot water
1.00.002185PTFE
Bronze 
(CAC407)
Stainless Steel 
(ASTM A351 
Gr.CF8)
1.6
CK3RScrewedBrass 
(C3604)
Air 
Hot water 
Water
1.00.00290NBR
Bronze 
(CAC407)
Stainless Steel 
(ASTM A351 
Gr.CF8)
1.6
CK3MGScrewedStainless Steel 
(ASTM A351 
Gr.CF8)
Steam 
Hot water 
Water
2.10.001220MetalSpecificationsManual
CKF3MWaferStainless Steel 
(ASTM A351 
Gr.CF8)
Steam 
Hot water 
Water
3.00.002350MetalSpecificationsManual
CKF3RWaferStainless Steel 
(ASTM A351 
Gr.CF8)
Air 
Hot water 
Water
1.60.002150FPM
CKF3MGWaferStainless Steel 
(ASTM A351 
Gr.CF8)
Steam 
Hot water 
Water
3.00.001350MetalSpecificationsManual
CKF3RGWaferStainless Steel 
(ASTM A351 
Gr.CF8)
Air 
Hot water 
Water
1.60.001150FPM
  • PMO = Maximum Operating Pressure
  • TMO = Maximum Operating Temperature
  • *When the valve has remained closed for a long period of time, the valve and the valve seat may stick, increasing the necessary minimum opening differential pressure.
  • The latest version of each product's instruction manual can be found on this page.

 